Reference Manual

All parameters are specified at 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM036A-EN-P — April 2014 15
Bulletin 1606 Switched Mode Power Supplies
15. Terminals and Wiring
Power terminals
Signal terminals
Type Bi-stable, quick-connect spring-
clamp terminals. IP20 Finger-
touch-proof. Suitable for eld-
and factory installation. Shipped
in open position.
Plug connector with screw terminal. Finger-touch-proof
construction with captive screws for 3.5mm slotted
screwdriver. Suitable for eld and factory installation.
Shipped in open position. To meet GL requirements,
unused terminal compartments should be closed.
Solid wire 0.5-6mm
2 2
0.2-1.5mm
2 2
Stranded wire 0.5-4mm 0.2-1.5mm
AWG 20-10AWG 22-14AWG
Ferrules Allowed, but not required Allowed, but not required
Pull-out force 10AWG:80N, 12AWG:60N,
14AWG:50N, 16AWG:40N
according to UL486E
Not applicable
Tightening torque Not applicable 0.4Nm, 3.5lb.in
Wire stripping length 10mm / 0.4inch 6mm / 0.24inch
Fig. 15-1 Spring-clamp terminals, connecting a wire
1.
Insert the wire
2.
Close the lever
To disconnect wire:
reverse the procedure
Instructions:
a)
Use appropriate copper cables, that are designed
for an operating temperature of 60°C
b)
Follow national installation codes and regulations.
c)
Ensure that all strands of a stranded wire are fully
inserted in the terminal connection.
d)
Up to two stranded wires with the same cross-
section are permitted in one connection point.
16. Reliability
Lifetime expectancy min. 137 400h At 10A output current, 40°C
min. > 15 years At 5A output current, 40°C
min. > 15 years At 10A output current, 25°C
MTBF SN 29500, IEC 61709 886 000h At 10A output current, 40°C
1 482 000h At 10A output current, 25°C
MTBF MIL HDBK 217F 397 900 At 10A output current , 40°C, ground benign GB40
545 000 At 10A output current , 25°C, ground benign GB25
The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specied in operational hours.
Lifetime expectancy is calculated according to the capacitor’s manufacturer specication. The prediction model allows
a calculation of up to 15 years from date of shipment.
MTBF stands for Mean Time Between Failures, which is calculated according to statistical device failures and indicates
reliability of a device. It is the statistical representation of the likelihood of failure of a given unit and does not
necessarily represent the life of a product.