Reference Manual Instruction Manual
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM007A-EN-P - February 2014 11
Bulletin 1606 Switched Mode Power Supplies
13. EMC
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environment without any restrictions. A detailed EMC report is available on request.
EMC Immunity
Generic standards: EN 61000-6-1 and EN 61000-6-2
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
8kV
Criterion A
Criterion A
Electromagnetic RF eld EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
4kV
2kV
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5
L N
N
PE, L PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + -
+
PE, - PE
1kV
2kV
Criterion A
Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
Mains voltage dips EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A *)
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
Voltage interruptions EN 61000-4-11 0Vac, 5000ms Criterion C
Input voltage swells Rockwell Automation internal standard 300Vac, 500ms Criterion A
Powerful transients VDE 0160 over entire load range 750V, 1.3ms Criterion A
Criteria:
A: Power supply shows normal operation behavior within the dened limits.
B: The power supply operates continuously during and after the test. During the test minor temporary impairments may occur, which will be
corrected by the power supply itself.
C: Temporary loss of function is possible. Power supply may shut down and restarts by itself. No damage or hazards for the power supply
will occur.
*) Up to 2A output current criterion A, above 2A output current criterion B.
EMC Emission
Generic standards: EN 61000-6-3 and EN 61000-6-4
Conducted emission EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B, input lines
Radiated emission EN 55011, EN 55022, CISPR 11, CISPR 22 Class B
Harmonic input current EN 61000-3-2 Not applicable below 75W
input power
Voltage uctuations,
icker *)
EN 61000-3-3 Fullled
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*) tested with constant current loads, non pulsing
Switching frequency
Converter frequency variable, typ. 100kHz, min. 45kHz, max. 160kHz Input voltage and output
load dependent