Reference Manual Manual

All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM016A-EN-P — February 2014 5
Bulletin 1606 Switched Mode Power Supplies
Fig. 3-5 De-rating requirements for
low input voltages
0
85Vac
10
20
30
40
50
60W
Input Voltage
A
.
.
.
<
+
4
5
°
C
B
.
.
.
<
+
6
0
°
C
A
B
90Vac 108Vac
Allowable
Output Power
4. Input Inrush Current
An electronic inrush current circuit limits the input inrush current after turn-on of the input voltage. The inrush current
is input voltage and ambient temperature independent.
The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current max. 8A
peak
8A
peak
8A
peak
between -40°C and +70°C
typ. 6A
peak
6A
peak
6A
peak
between -40°C and +70°C
Inrush energy max. 0.2A
2
s 0.2A
2
s 0.3A
2
s between -40°C and +70°C
Fig. 4-1 Input inrush current, typical behavior
Input Voltage
Input Current
Output Voltage
Input: 230Vac
Output: 12V, 4.5A
Ambient: 25°C
Upper curve: Input current 2A/DIV
Middle curve: Input voltage 200V/DIV
Lower curve: Output voltage 2.5V/DIV
Time basis: 20ms / DIV