All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM016A-EN-P — February 2014 21
Bulletin 1606 Switched Mode Power Supplies
20.11. Use at Low Temperatures (-25°C to -40°C)
Please pay attention to the following factors when operating the unit at low te mperatures. Perform tests to verify
suitability in your application.
- The ripple & noise voltage will increase. For the rst minutes after turning on the unit at -40°C, the ripple and
noise voltage can be up to typically 400mVpp depending on load and input voltage. Once the unit heats up,
the ripple & noise voltage will decrease typically to 90mVpp.
- The start-up delay can be up to 5 seconds. It is a continuous turn-on process without any voltage dips or start-
up attempts.
20.12. Use in a Tightly Sealed Enclosure
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature denes the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box; no other heat producing item is inside the box.
Enclosure: Rittal Type IP66 Box PK 9510 100, plastic, 130x130x75mm
Input: 230Vac
Case A:
Load: 12V, 4.5A; load is placed outside the box.
Temperature inside the box: 42.3°C (in the middle of the right side of the power supply with a distance of 1cm)
Temperature outside the box: 21.7°C
Temperature rise: 20.6K
Case B:
Load: 12V, 3.6A; (=80%) load is placed outside the box.
Temperature inside the box: 40.6°C (in the middle of the right side of the power supply with a distance of 1cm)
Temperature outside the box: 21.9°C
Temperature rise: 18.7K