Reference Manual Manual
All parameters are specified at 12V, 4.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
12 Rockwell Automation Publication 1606-RM016A-EN-P — February 2014
Bulletin 1606 Switched Mode Power Supplies
14. Environment
Operational temperature
*) -40°C to +70°C (-40°F to 158°F) reduce output power according Fig. 14-1
Storage temperature -40°C to +85°C (-40°F to 185°F) for storage and transportation
Output de-rating 1.4W/°C 60-70°C (140°F to 158°F)
Humidity **) 5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Shock 15g 6ms, 10g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
Altitude 0 to 2000m (0 to 6 560ft) without any restrictions
2000 to 6000m (6 560 to 20 000ft) reduce output power or ambient temperature
see Fig. 14-2
IEC 62103, EN 50178, overvoltage category II
Altitude de-rating 4W/1000m or 5°C/1000m > 2000m (6500ft), see Fig. 14-2
Over-voltage category III IEC 62103, EN 50178, altitudes up to 2000m
II altitudes from 2000m to 6000m
Degree of pollution 2 IEC 62103, EN 50178, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
*) Operational temperature is the same as the ambient temperature and is dened as the air temperature 2cm below the unit.
Do not connect or disconnect the wires from the terminals below -25°C.
**) Do not energize in the presence of condensation.
Fig. 14-1 Output power vs. ambient temp. Fig. 14-2 Output power vs. altitude
0
-40 0 40
70°C
10
20
30
40
50
60W
60
A... for AC 230V mains
B... for AC 120V mains
C... for AC 100V mains
-25-33
Ambient Temperature
Allowable
Output Power
A
C
B
0
0 2000 4000
6000m
10
20
30
40
50
60W
Altitude
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
A
B
C
Allowable
Output Power