Reference Manual Owner's manual

All parameters are specified at 124V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
22 Rockwell Automation Publication 1606-RM006A-EN-P - January 2014
Bulletin 1606 Switched Mode Power Supplies
20.11.Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
inuences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 20-5
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Output Power
0
10 20 30 40
60°C
6
18
24
30W
50
A
1
12
Ambient Temperature
Fig. 20-6
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPUT
Output Power
0
10 20 30 40
60°C
6
18
24
30W
50
12
A
1
A
2
Ambient Temperature
Fig. 20-7
Mounting
Orientation C
(Table-top
mounting)
Output Power
0
10 20 30 40
60°C
6
18
24
30W
50
12
A
1
A
2
Ambient Temperature
Fig. 20-8
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Power
0
10 20 30 40
60°C
6
18
24
30W
50
12
A
1
A
2
Ambient Temperature
Fig. 20-9
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Output Power
0
10 20 30 40
60°C
6
18
24
30W
50
12
A
1
A
2
Ambient Temperature