Reference Manual User guide
All parameters are specified at 12V, 2.5A,230Vac input, 25ªC ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM030A-EN-P — April 2014 21
Bulletin 1606 Switched Mode Power Supplies
22.11. Mounting Orientations
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximal allowed ambient temperature. The amount of reduction
inuences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 22-5
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2
4
6
8A
50
A
1
Ambient Temperature
Fig. 22-6
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2
4
6
8A
50
Ambient Temperature
A
2
A
1
Fig. 22-7
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30 40
60°C
2
4
6
8A
50
Ambient Temperature
A
1
A
2
Fig. 22-8
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2
4
6
8A
50
Ambient Temperature
A
1
A
2
Fig. 22-9
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Output Current
0
10 20 30 40
60°C
2
4
6
8A
50
Ambient Temperature
A
1
A
2