Reference Manual User guide

2 Rockwell Automation Publication 1606-RM030A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
Power Supply
AC 380-480V Wide-range Input
Input Fuses Already Included
Requires only Two Legs of a 3-Phase System
Width only 40mm
Efciency up to 85.8%
Input -Transient Blanking Circuit Included
Minimal Inrush Current Surge
Full Power Between -25°C and +60°C
3 Year Warranty
Description
Our power supplies are cost optimized without
compromising quality, reliability or performance. The
most outstanding features of the 1606-XLE96B-2 are its
high efciency, electronic inrush current limitation, active
input transient lter and wide operational temperature
range. It distinguishes itself by its small size and other
technological design breakthroughs.
The 1606-XLE96B-2 includes all the essential basic functions.
It utilizes only two legs of a three-phase system which saves
on wiring and installation costs. Furthermore, this concept
allows you to use a smaller unit without compromising the
size of the terminals. Due to the low power consumption,
an unbalancing of the individual phases is not expected.
Specication Quick Reference
Output voltage DC 12V
Adjustment range 12-15V
Output current 8 – 6.4A
Output power 96W
Output ripple < 100mVpp 20Hz to 20MHz
Input voltage AC 380-480V -15%/+20%
Mains frequency 50-60Hz ±6%
AC Input current 0.64 / 0.56A at 400 / 480Vac
Power factor 0.44 / 0.42 at 400 / 480Vac
AC Inrush current typ. 4A peak
Efciency 85.4 / 85.8% at 400 / 480Vac
Losses 16.4 / 15.9W at 400 / 480Vac
Temperature range -25°C to +70°C operational
Derating 2.5W/°C +60 to +70°C
Hold-up time typ. 33 / 58ms at 400 / 480Vac
Dimensions 40x124x117mm WxHxD
Catalog Numbers
Power Supply 1606-XLE96B-2 12-15V Standard unit
Accessories 1606-XLB Wall mount bracket
1606-XLSRED Decoupling
module
Certication Marks
IND. CONT. EQ.
UL 508
UL 60950-1
Marine
EMC, LVD
Marine RINA
GOST R
C-Tick