Reference Manual User guide
2 Rockwell Automation Publication 1606-RM030A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
Power Supply
AC 380-480V Wide-range Input
Input Fuses Already Included
Requires only Two Legs of a 3-Phase System
Width only 40mm
Efciency up to 85.8%
Input -Transient Blanking Circuit Included
Minimal Inrush Current Surge
Full Power Between -25°C and +60°C
3 Year Warranty
Description
Our power supplies are cost optimized without
compromising quality, reliability or performance. The
most outstanding features of the 1606-XLE96B-2 are its
high efciency, electronic inrush current limitation, active
input transient lter and wide operational temperature
range. It distinguishes itself by its small size and other
technological design breakthroughs.
The 1606-XLE96B-2 includes all the essential basic functions.
It utilizes only two legs of a three-phase system which saves
on wiring and installation costs. Furthermore, this concept
allows you to use a smaller unit without compromising the
size of the terminals. Due to the low power consumption,
an unbalancing of the individual phases is not expected.
Specication Quick Reference
Output voltage DC 12V
Adjustment range 12-15V
Output current 8 – 6.4A
Output power 96W
Output ripple < 100mVpp 20Hz to 20MHz
Input voltage AC 380-480V -15%/+20%
Mains frequency 50-60Hz ±6%
AC Input current 0.64 / 0.56A at 400 / 480Vac
Power factor 0.44 / 0.42 at 400 / 480Vac
AC Inrush current typ. 4A peak
Efciency 85.4 / 85.8% at 400 / 480Vac
Losses 16.4 / 15.9W at 400 / 480Vac
Temperature range -25°C to +70°C operational
Derating 2.5W/°C +60 to +70°C
Hold-up time typ. 33 / 58ms at 400 / 480Vac
Dimensions 40x124x117mm WxHxD
Catalog Numbers
Power Supply 1606-XLE96B-2 12-15V Standard unit
Accessories 1606-XLB Wall mount bracket
1606-XLSRED Decoupling
module
Certication Marks
IND. CONT. EQ.
UL 508
UL 60950-1
Marine
EMC, LVD
Marine RINA
GOST R
C-Tick