User Manual
All parameters are specified at 48V, 20A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
6 Rockwell Automation Publication 1606-RM025A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
7. Output
Output voltage nom. 48V
Output voltage adjustment range
none The output voltage is xed. No ajustment possible.
Output current
nom. 20A continuous, see Fig. 7-1
25A up to 15s with full output voltage, see Fig. 7-1
Short-circuit current
typ. 90A load impedance 50mOhm, see Fig. 7-1
Note: The short-circuit current is available for 0.1s.
Output power
nom. 960W continuous
1200W up to 15s
Line regulation
max. ±2% see Fig. 5-1
Load regulation max. 1600mV static value, 0A 20A 0A
max. 100mV static value, 2.5A 20A 2.5A
Ripple and noise voltage *)
max. 2500mVpp 20Hz-2kHz, 50Ohm
max. 300mVpp 2kHz to 20MHz, 50Ohm
Output capacitance
typ. 7 600μF
*) The ripple and noise voltage mostly consist of a mains ripple with 300Hz (50Hz mains) or 360Hz (60Hz mains). The ripple and
noise voltage can be reduced by the utilization of external capacitors.
The power supply is also designed to support loads with a higher short-term current and power requirement. The
short-term duration is rmware controlle d by an output power manager. If the nominal output power is exceeded for
a certain period of time which is dened in zone A, B and C, the power supply responds with an automatic shut-down.
Pressing the reset button or cycling the input power (10s o time is required) initiates a restart attempt. If the fault has
been cleared the device will operate normally.
The short term power can be used periodically . See section 25.1 for further information.
Fig. 7-1 Output voltage vs. output current, typ.
V
OUT
20A A07A5240A0
A
15s
48V
100A
30A A09A08A06A05A01
24V
I
OUT
B
5s
C
0.1s
3x 408V
3x 480V
3x 552V
1606-XLE960MX-3N
Zone A
:
25% extra output power for typ. 15s
Zone B
:
100% higher output current for typ. 5s
Zone C:
Quick-acting shut-down after typ. 0.1s