Reference Manual Owner's manual
All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
6 Rockwell Automation Publication 1606-RM024A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
7. Output
Output voltage nom. 24.1V
Output voltage adjustment range
none The output voltage is xed. No adjustment possible.
Output current
nom. 40A continuous, see Fig. 7-1
50A up to 15s with full output voltage, see Fig. 7-1
Short-circuit current
typ. 180A load impedance 25mOhm, see
Fig. 7-1
Note: The short-circuit current is available for 0.1s.
Output power
nom. 960W continuous
1200W up to 15s
Line regulation
max. ±2% see Fig. 5-1
Load regulation max. 800mV static value, 0A 40A 0A
max. 200mV static value, 5A 40A 5A
Ripple and noise voltage *)
max. 1500mVpp 20Hz-2kHz, 50Ohm
max. 50mVpp 2kHz to 20MHz, 50Ohm
Output capacitance
typ. 20 000μF
*) The ripple and noise voltage mostly consist of a mains ripple with 300Hz (50Hz mains) or 360Hz (60Hz mains). The ripple and
noise voltage can be reduced by using external capacitors.
The power supply is also designed to support loads with a higher short-term current and power requirement. The
short-term duration is rmware-controlled by an output power manager. If the nominal output power is exceeded for
a certain period of time which is dened in zone A, B and C, the power supply responds with an automatic shut-
down. Pressing the reset button or cycling the input power (10s o time is required) initiates a restart attempt.
If the fault has been cleared the device will operate normally.
The short term power can be used periodically . See section 25.1 for further information.
Fig. 7-1 Output voltage vs. output current, typ.
V
OUT
40A A041A0580A
0
A
15s
24V
200A60A A081A061A021A001
A02
12V
I
OUT
B
5s
C
0.1s
3x 408V
3x 480V
3x 552V
Zone A : 25% extra output power for typ. 15s
Zone B:
100% higher output current for typ. 5s
Zone C:
Quick-acting shut-down after typ. 0.1s