Reference Manual Owner's manual
All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
4 Rockwell Automation Publication 1606-RM024A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
5. AC-Input
1606-XLE960DX-3N
AC input nom. 3AC 480V
Mains arrangement
TN-, TT- or IT-Mains. Consult factory if one phase is grounded.
AC input range
min.
3x 432-528Vac
fully regulated output (±2%), Pout > 48W
min. 3x 360-552Vac
*)
permanently allowed,
see Fig. 5-1 for output voltage regulation
max. 3x 565Vac Absolute maximum input voltage with no
damage to the power supply. Output
might be o at this level.
Input frequency
nom. 50 – 60Hz ±6%
Turn-on voltage typ. 3x 390Vac see
Fig. 5-2
Shut-down voltage typ.
3x 355Vac see Fig. 5-2
Input current
nom. 1.4A at 40A, symmetrical input, see Fig. 5-4
Power factor **) typ. 0.93 at 40A, symmetrical input, see Fig. 5-5
Turn-on overshoot typ. 480mV see
Fig. 5-3
Start-up delay ***) typ. 350ms over the entire load range, see Fig. 5-3
Rise time typ. 40ms 0mF, 40A, see
Fig. 5-3
typ. 70ms 40mF, 40A, see
Fig. 5-3
*) A minimum voltage of 3x408Vac is required to turn the power supply on.
**) The power factor is the ratio of the true (or real ) power to the apparent power in an AC circuit.
***) The start-up delay for mains voltage interruptions up to 350ms is close to zero. In such cases, the power supply will
immediately generate the output voltage once the mains voltage interruption is over. Do not use the 1606-XLSBUFFER24
buer module as an accessory when longer mains interruptions need to be bridged (see section 23).
Input Voltage Range
Fig. 5-1
Output voltage vs. input voltage and input current
Changes of the input voltage will be fully
regulated within certain limits. The
output voltage will only start to change
proportionally to the input voltage with
extreme under or over-voltages. The
yellow LED reports an input voltage
problem if exceeded by a window of
±15%. The maximum increase of the
output voltage is limited to the 29.9V
OVP level. This level will be kept
regulated for 2s before the power supply
will shut down and re ports “Shut-down”
by the red LED.
24V
20V
26V
22V
504456 576Vac384
V
OUT
V
IN
1606-XLE: 480
28V
528 552432408 360
P
OUT
> 48W (5%)
P
OUT
= 0W