Reference Manual Owner's manual

All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM024A-EN-P — April 2014 13
Bulletin 1606 Switched Mode Power Supplies
16. Protection Features
Output protection Electronically protected against overload, no-load and short-circuits
*)
Output overvoltage protection max. 29.9Vdc in case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Input overvoltage shutdown typ. 3x 560Vac 1606-XLE960DX-3N
Degree of protection IP 20 EN/IEC 60529
Penetration protection > 3.5mm e.g. screws, small parts
Over-temperature protection yes output shut-down with automatic restart
Input transient protection MOV (Metal Oxyde Varistor) and active transient blocker
Internal input fuse not included see section 25.4
*) An audible noise may be heard during a no-load, overload or short circuit event.
17. Safety
Input/output separation SELV IEC/EN 60950-1
PELV
double or reinforced insulation
EN 60204-1, EN 50178, IEC 60364-4-41
Class of protection I PE (Protective Earth) connection required
Isolation resistance > 5MOhm input to output, 500Vdc
PE resistance < 0.1Ohm between housing and PE terminal
Touch current (leakage current) typ. 0.40mA 13x480V, 60Hz, TN mains
< 0.45mA 3x524V, 60 Hz, TN mains
18. Dielectric Strength
Fig. 18-1 Dielectric strength
A B C
Type test 60s 2500Vac 3000Vac 500Vac
Factory test 5s 2500Vac 2500Vac 500Vac
Field test 5s 2000Vac 2000Vac 500Vac
A
C
B
L1
Input
Earth
Output
-
+
L3
L2
Type tests and factory tests:
Conducted by the manufacturer. Do not repeat these tests in
the eld!
Rules for eld test:
Use appropriate test equipment which applies the voltage
with a slow ramp! Connect L1, L2 and L3 together as well as
all output poles.
The output voltage is oating and has no ohmic connection to ground. Grounding of output is allowed.
To fulll the PELV requirements according to EN60204-1, paragraph 6.4.1, we recommend that either + pole or
the – pole be connected to the protective earth system. This helps avoid situations in which a load starts
unexpectedly or cannot be switched o when an unnoticed ground fault occurs.