Reference Manual Owner's manual
All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
12 Rockwell Automation Publication 1606-RM024A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
15. Environment
Operational temperature -25°C to +70°C (-13°F to 158°F) Reduce output power above +60°C
ees ,)F°851 ot F°041( C°07-06 24W/°C Output derating Fig. 15-1
Storage temperature -40 to +85°C (-40°F to 185°F) storage and transportation
.H.r %59 ot 5 ytidimuH
no condensation allowed
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
IEC 60068-2-6
Vibration random
0.5m
2
(s
3
)
2 hours / axis
IEC 60068-2-64
Shock
15g 6ms, 10g 11ms
3 bumps / direction, 18 bumps in total
IEC 60068-2-27
tneibma ro rewop tuptuo ecudeR )tf000 02 ot 0( m0006 ot 0 edutitlA
temperature above 2000m sea level.
Output derating (for altitude) 60W/1000m or 5°C/1000m above 2000m, see Fig. 15-2.
NE III Over-voltage category
50178, altitudes up to 2000m
m0006 ot m0002 morf sedutitlA II
evitcudnoc non ,87105 NE 2 noitullop fo eergeD
Fig. 15-1 Output current vs. ambient temp., Fig. 15-2 Output current vs. altitude
Allowed
Output Current
0
-25 0 20 40
70°
C
10
20
30
40A
60
Ambient Temperature
Allowed Output
Current
0
0 2000 4000
6000m
10
20
30
40A
Altitude
A
.
.
.
T
a
m
b
<
6
0
°
C
B
.
.
.
T
a
m
b
<
5
0
°
C
C
.
.
.
T
a
m
b
<
4
0
°
C
A
B
C
The ambient temperature is dened 2cm below the unit.