Reference Manual Owner's manual

All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM024A-EN-P — April 2014 11
Bulletin 1606 Switched Mode Power Supplies
14. EMC
The power supply is suitable for applications in industrial environments as well as in residential, commercial and light
industry environment without any restriction. The CE Mark indicates conformance with EMC guideline 89/336/EC,
93/68/EC and the low-voltage directive (LVD) 73/23/EC, 93/68/EC and 2006/95/EC.
A detailed EMC Report is available upon request.
EMC Immunity
EN 61000-6-1, EN 61000-6-2 Generic standards
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF eld EN 61000-4-3 80MHz-1GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
4kV
4kV
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5 L1
L1 / L2 / L3
+ -
2kV
4kV
500V
Criterion A
Criterion A
Criterion A
-
+
PE
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
EMC Emission
EN 61000-6-3 and EN 61000-6-4 Generic standards
Conducted emission EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B, input lines
Class B, output lines
Radiated emission EN 55011, EN 55022 Class B
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching frequency
Switching frequency 36kHz Nearly constant
EN 55022
L2, L2 L3, L1 L3
PE
Surge voltage on output EN 61000-4-5
500V
Criterion A
Mains voltage dips EN 61000-4-11 0% of 400Vac 20ms Criterion B
40% of 400Vac 200ms Criterion C
70% of 100Vac 500ms Criterion C
0% of 480Vac 20ms Criterion B
40% of 480Vac 200ms Criterion C
70% of 480Vac 500ms Criterion C
Power transients VDE 0160 over entire load range 1300V, 1.3ms Criterion D
Criteria:
A: Power supply shows normal behavior within the dened limits.
B: During the mains voltage dip, the output voltage will decrease according to curves in the Hold-up Time section. Unit works in normal
mode after the voltage dip. If criterion A is required, use one or two buffer modules in addition to the 1606-XLE960DX-3N supply.
C: Temporary loss of function is possible. Power supply may shutdown and restart by itself. No damage or hazard to the power supply occurs.
D: The input transient blocker opens and the main converter is without input power during such transients. The output voltage decreases as
well, as described in the Hold-up Time section, during such an event.
Harmonic input current EN 61000-3-2 Fullled, active PFC
Voltage uctuations, icker EN 61000-3-3 Fullled