All parameters are specified at 24V, 40A, 3x480Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
10 Rockwell Automation Publication 1606-RM024A-EN-P — April 2014
Bulletin 1606 Switched Mode Power Supplies
12. Terminals and Wiring
Use appropriate copper cables that are designed for a minimum operating temperatures of 60°C (for ambient up to
45°C) and 75°C (for ambient up to 60°C). Follow national installation codes and regulations! Ensure that all strands of
a stranded wire enter the terminal connection! Do not use the power supply without PE (Ground) connection! Up to
two stranded wires with the same cross section are permitted in one connection point (except PE wire). Ferrules are
allowed, but not required.
Output Input
lanimret wercS lanimret wercS epyT
mm6-5.0 eriw diloS
2
mm61-5.0
2
mm4-5.0 eriw dednartS
2
mm01-5.0
2
GWA 8-22 GWA 01-02 eguag eriw naciremA
Wire stripping length 7mm / 0.26inch 12mm / 0.5inch
Recommended tightening torque 0.8Nm / 7lb.inch 1.2Nm / 10.6lb.inch
13. Reliability
Lifetime expectancy min. 51 000h 40°C, 24.1V, 40A
A04 ,V1.42 ,C°52 h000 241 .nim
A04 ,V1.42 ,C°04 h000 925 90716 CEI ,00592 NS FBTM
A04 ,V1.42 ,C°52 h000 959
°
04 h000 602 F712 KBDH LIM FBTM C, 24.1V, 40A, Ground Benign GB40
276 000h 25°C, 24.1V, 40A, Ground Benign GB25
The Lifetime expectancy shown in the table above indicates the operating hours (service life) and is determined by
the lifetime expectancy of the built-in electrolytic capacitors.
Lifetime expectancy is specied in operational hours and is calculated according to specications from the
manufacturer of the capacitor. The prediction model allows a calculation up to 15 years from the shipping date.
MTBF stands for Mean Times Between Failures which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of failure of the unit, and does not necessarily
represent the life of a product.