User guide

A-2 Specifications
All Drive Ratings Table A.3
Input/Output Ratings
Output Voltage Adjustable from 0 to Input Voltage
Output Frequency Programmable from 0 to 240 Hz
Efciency 97.5% Typical
Transient Protection Standard 6 kV
Environmental Specications
Enclosure IP20
Ambient Temperature 0°C to 50°C
Storage Temperature
40°C to 85°C
Relative Humidity 0 to 95% Non-Condensing
Vibration 1.0 G Operational 2.5 G Non-Operational
Shock 15 G Operational 30 G Non-Operational
Altitude 1,000 m (3,300 ft) without Derating
Control Inputs
Control Input Type Dry Contact Inputs Drive has an internal 12V power supply that provides 10
mA typical current ow.
Alternate Inputs Accepts open collector/solid state inputs (sinking into the
drive) with maximum leakage current of 50 µA.
24V Inputs An optional 24V DC interface module allows use of 24VDC
sinking inputs (see ).
Start, Stop, Fwd/Rev
Congurable Inputs for Two- or Three-Wire Control
SW1, SW2, SW3
Preset Speed Model Only
Congurable Inputs for Control of 8 Preset Speeds and 2 Accel/Decel Times
Programmable Input
TB3-8 Can Be Congured to Select:
Accel/Decel Times
External Coast to Rest
TB3 Control/Keypad or Communication Control
Frequency Select
Preset Speed
Approvals and Standards Compliance
Approvals
Designed to Meet These Standards FCC Class A
and B , IEC 146-1-1, VDE 0871 and VDE 0875
Control Inputs Analog Signal Follower Only
External Speed
Potentiometer
1K to 10K Ohms, 2 Watts Minimum
4 20 mA Analog Input
250 Ohms Input Impedance
10 to +10V DC
Analog Input
100K Ohms Input Impedance
Control Output
Programmable Output
(Form C Relay Contact)
Resistive Rating: 0.4A at 125VAC 0.2A at 230V AC 2A at 30VDC
Inductive Rating: 0.2A at 125VAC 0.1A at 230V AC 1A at 30V DC
Analog Signal Follower only.
With external components.
U
L
®
L
I
S
T
E
D
9
6
6
X
I
N
D
C
O
N
T
E
Q
UL508C
U
L
®
L
I
S
T
E
D
9
6
6
X
I
N
D
C
O
N
T
E
Q
C
CSA 22.2 AS/NZS 2064.1:1992
EMC Directive 89/336
LV: EN 50178, EN 60204