User guide
5-10 Parameters and Programming
47 [Output Configure]
Configures the TB3 relay output functionality.
0/10 Numeric
Value
0
48 [Output Threshold]
Determines the on/off point for the TB3 output relay when P47 - [Output Configure]
is set to 6, 7, 8, and 10.
Setting Ranges
6 0 to 240 Hz
7 0 to 180%
8 0 to 815 Volts
10 0 to 180˚
0/815 Numeric
Value
0
49 [PWM Frequency]
Carrier frequency for the PWM output waveform. The chart below provides
derating guidelines based on the PWM frequency setting.
Important: Ignoring derating guidelines can cause reduced drive performance.
2.0/8.0 0.1 kHz 4.0 kHz
50 [Restart Tries]
Maximum number of times the drive will attempt to reset a fault.
Faults 03 – 20 will automatically reset according to this parameter setting.
0/9 Numeric
Value
0
Program Group
No. Parameter Name/Description
Min./Max.
Range
Units
Factory
Default
Setting Output Changes State When . . .
0 Drive Ready/Faulted Energized and returns to shelf state when power is
removed or a fault occurs.
1 At Frequency Drive reaches commanded frequency.
2 Motor Running The motor is receiving power from drive.
3 Reverse Drive is commanded to run in the reverse direction.
4 Motor Overload A motor overload condition exists.
5 Ramp Regulated The ramp regulator is modifying the programmed accel/
decel times to avoid an overcurrent or overvoltage fault
from occurring.
6 Above Frequency The drive exceeds the frequency value set in
P48 - [Output Threshold].
7 Above Current Drive exceeds the value set in P48 - [Output Threshold].
Important: Value for P48 - [Output Threshold] must be
entered in percent of drive rated output current.
8 Above DC Bus Voltage Drive exceeds the DC bus voltage value set in
P48 - [Output Threshold].
9 Retries Exhausted Number of retries for P50 - [Restart Tries] is exceeded.
10 Above Power Factor
Angle
Power Factor angle exceeds the value set in
P48 - [Output Threshold].
1
2345678
84
86
88
90
92
94
96
98
100
% Output Current (A)
Carrier Frequency (kHz)