Quick Reference Card Owner's manual

Fault Codes
Fault
No. Fault Indication and Corrective Action
03 Power Loss Fault
Monitor incoming AC line for low voltage or line power
interruption.
04 UnderVoltage Fault
Monitor incoming AC line for low voltage or line power
interruption.
05 OverVoltage Fault
Bus overvoltage caused by motor regeneration. Monitor
incoming AC line for excessive voltage. Extend the decel
time or install dynamic brake module or external capaci-
tor module.
06 Motor Stall Fault
Longer acceleration time or a reduced load required.
07 Motor Overload Fault
Reduce motor load until drive output current does not
exceed the current set by P42 - [Motor Overload
Current]. Reduce P38 - [Boost Select].
08 Over Temperature Fault
Clear blocked or dirty heat sink fins. Check ambient tem-
perature. Check for blocked or non-operating fan.
11 Operator Error
Clear fault. Do not remove keypad under power.
12 Overcurrent FauIt
Check short circuit at the drive output or excessive load
conditions at the motor.
13 Software Overcurrent Fault
A longer acceleration time, reduced load, or removal of
motor shaft blockage is required.
Parameter 07 - [Active Fault]
Fault Number
IMPORTANT: This publication is designed as a reference
tool. The 160 SSC User Manual (publication 0160-5.15) must
be consulted for more detailed information about parameters,
faults and hazards of personal injury.
160 SSC™ Variable
Speed Drive
Quick Reference
Series C, FRN 7.xx
Publication 0160-5.16 – June, 2000 P/N 189339 (02)
Supersedes October, 1998
20 Drive Overload Fault
Clear blocked or dirty heat sink fins. Check ambient tem-
perature. Check for blocked or non-operating fan.
Reduce motor load current.
32 EEPROM Fault
Reset EEPROM using P56 - [Reset Functions]. Set to 1.
Cycle Power
33 Max Retries Fault
Repair system fault.
36 Incompatible Fault
Check the wiring between the drive and the motor.
Check the motor for a grounded phase.
38 Phase U Fault
Check the wiring between the drive and motor. Check
motor for grounded phase.
39 Phase V Fault
Check the wiring between the drive and motor. Check
motor for grounded phase.
40 Phase W Fault
Check the wiring between the drive and motor. Check
motor for grounded phase.
41 UV Short Fault
Check the motor and external wiring to the drive output
terminals for a shorted condition.
42 UW Short Fault
Check the motor and external wiring to the drive output
terminals for a shorted condition.
43 VW Short Fault
Check the motor and external wiring to the drive output
terminals for a shorted condition.
46 Intermittent Power Output Fault
Check the wiring between the drive and motor. Check
the motor for more than one shorted output.
48 Reprogram Fault
Clear fault.
These faults have an auto reset feature. This feature automatically clears overvolt-
age, undervoltage and overtemperature faults 1 second after the fault condition is
removed. Refer to P51 - [Restart Time].