Manual

Publication 0160-5.5 - September 1997
C-2 ODVA Interface Parameter Descriptions
ODVA Drive Profile Interface
Parameters (Continued)
Parameter
Number
Parameter
Group
Name and Description
Object
Mapping
(Class-
Instance-
Attribute)
Min./Max.
Range
Units
Factory
Default
01 Motor [Motor Rated Current]
This read/writeparameter isset to themotor nameplate fullload Amp rat-
ing (FLA). The drive uses this value as the motor overload setting.
0x28-1-6 0 to 24.00
Amperes
0.01
Amperes
Drive
Rating
02 Motor [Motor Rated Volt]
This read/write parameter is set to the motor nameplate voltage. The
drive uses this value in its volts/Hz calculations.
0x28-1-7 0 to 460
Volts
1 Volt Drive
Rating
03 Motor [Motor Rated Frequency]
Thisread/write parameterisset tothemotor nameplateratedFrequency.
This value is used by the drive in its volts/Hz calculations.
0x28-1-9 10 to 240
Hz
1 Hz 60
Hz
04 Motor [Motor Base Speed]
This read/write parameter is set to the motor’s rated nameplate speed in
RPM.
0x28-1-15 200 to
32,000
RPM
1 RPM 1800
RPM
05 Control
Supervisor
[Network Control]
This read/write parameter determines whether Run/Stop control is local
(TB3) or from the network.
0 = Control from TB3.
1 = Network Control.
Important: Power must be cycled for actual control to change sources,
and actual control status is reflected in P13 - [Control From Net].
0x29-1-5 0 to 1 Numeric
Value
0
06 Control
Supervisor
[Drive State]
This read only parameter returns the status of the drive state.
1 = Startup.
3 = Ready.
4 = Enabled.
7 = Faulted.
0x29-1-6 1 to 7 Numeric
Value
07 Control
Supervisor
[Running Fwd]
This read only parameter reflects the running forward state of the drive.
1 = Drive is running forward.
0 = Drive is not running forward.
0x29-1-7 0 to 1 Numeric
Value
08 Control
Supervisor
[Running Rev]
This read only parameter reflects the running reverse state of the drive.
1 = Drive is running reverse.
0 = Drive is not running reverse.
0x29-1-8 0 to 1 Numeric
Value