B-14 DeviceNet Information
Class Code 0xB3 —
160 Parameter Table Object
Instance 1 Attributes:
Class Attributes: None Supported Number of Instances: 1
Attribute ID
Access
Rule
Parameter Name
Data
Type
Units Description
This Bulletin 160 SSC specific object implements all of the parameters in the 160 SSC parameter table as instance attributes of the object. For example,
attribute #1 corresponds to P01 - [Output Frequency]. This give you the ability to configure a drive via DeviceNet using attribute numbers that are pub-
lished asparameter numbersin theBulletin 160 SSCUser Manual.Important:Attributes9 and12 shownbelow donot match whatis published inthe Bul-
letin 160 SSC User Manual.
01 Get [Output Frequency] UINT 0.1 Hz Frequency at TB2 terminals T1, T2, T3.
02 Get [Output Voltage] UINT 1 Volt Voltage at TB2 terminals T1, T2, T3.
03 Get [Output Current] UINT 0.01 Amperes Current at TB2 terminals T1, T2, T3.
04 Get [Output Power] UINT 0.01 kW Power at TB2 terminals T1, T2, T3.
05 Get [Bus Voltage] UINT 1 Volt DC Bus voltage level.
06 Get [Frequency Command] UINT 0.1 Hz Commanded frequency.
07 Get [Last Fault] USINT Numeric Value Coded last fault number.
08 Get [Heatsink Temp] USINT 1 C Temperature of the drive heatsink.
09 Get [Drive Status] USINT Binary Number Status of drive in binary coded format.
10 Get [Drive Type] UINT Numeric Value Used by Allen-Bradley field service personnel.
11 Get [Control version] UINT Numeric Value version of drive firmware used.
12 Get [Input Status] USINT Binary Number Open (0) Closed (1) state of drive’s discrete inputs.
13 Get [Power Factor Angle] UINT 0.1 Angle (electrical degrees) between V and I.
14 Get [Memory Probe] UINT Numeric Value Used by Allen-Bradley service personnel.
16 Get [Analog Input] INT 0.1% The analog input as a percent of full scale.
30 Get/Set [Accel Time 1] UINT 0.1 Seconds Time to ramp from 0 Hz to maximum frequency.
31 Get/Set [Decel Time 1] UINT 0.1 Seconds Time to ramp from maximum frequency to 0 Hz.
32 Get/Set [Minimum Frequency] USINT 1 Hz Lowest continuous output frequency.
33 Get/Set [Maximum Frequency] USINT 1 Hz Highest continuous output frequency.
34 Get/Set [Stop Mode Select] USINT Numeric Value Determines stop mode used.
35 Get/Set [Base Frequency] USINT 1 Hz Set to motor’s nameplate frequency.
36 Get/Set [Base Voltage] UINT 1 Volt Set to motor’s nameplate voltage.
37 Get/Set [Max Voltage] UINT 1 Volt Highest voltage the drive will output.
38 Get/Set [Boost Select] USINT Numeric Value Sets the volts/Hz relationship.
!
ATTENTION: Changing this parameter
value may cause unpredictable network
conditions,resultinginequipmentdamage,
personal injury, or death. Ensure that you
understand how changing this parameter
affects your application.