Manual
Publication 0160-5.5 - September 1997
C-10 ODVA Interface Parameter Descriptions
ODVA Drive Proļ¬le Interface
Parameters (Continued)
Parameter
Number
Parameter
Group
Name and Description
Object
Mapping
(Class-
Instance-
Attribute)
Min./Max.
Range
Units
Factory
Default
63 Preset [DN Preset Cmd]
This read/write parameter acts as the network preset command.
0x2A-1-192 0 to 7 Numeric
Value
0
64 Preset [Preset RPM 0]
This read/write parameter sets the speed that the drive outputs when
selected.
0x2A-1-161 0 to 32000 1 RPM 90 RPM
65 Preset [Preset RPM 1]
This read/write parameter sets the speed that the drive outputs when
selected.
0x2A-1-162 0 to 32000 1 RPM 600 RPM
66 Preset [Preset RPM 2]
This read/write parameter sets the speed that the drive outputs when
selected.
0x2A-1-163 0 to 32000 1 RPM 900 RPM
67 Preset [Preset RPM 3]
This read/write parameter sets the speed that the drive outputs when
selected.
0x2A-1-
164
0 to 32000 1 RPM 1200 RPM
68 Preset [Preset RPM 4]
This read/write parameter sets the speed that the drive outputs when
selected.
0x2A-1-
165
0 to 32000 1 RPM 1350 RPM
69 Preset [Preset RPM 5]
This read/write parameter sets the speed that the drive outputs when
selected.
0x2A-1-
166
0 to 32000 1 RPM 1500 RPM
70 Preset [Preset RPM 6]
This read/write parameter sets the speed that the drive outputs when
selected.
0x2A-1-
167
0 to 32000 1 RPM 1650 RPM
71 Preset [Preset RPM 7]
This read/write parameter sets the speed that the drive outputs when
selected.
0x2A-1-
168
0 to 32000 1 RPM 1800 RPM
72 Preset [Accel Time 2]
Thisread/write parametersets theaccelerationtimeforparameters68 to
71 (preset RPM 4-7).
0x2A-1-
169
100 to
65500
1ms 20000 ms
72 AC Drive
Extension
[Accel Time 2]
This read/write parameter sets the acceleration time.
0xB3-1-69 0-60000 1 ms 20000 ms
73 Preset [Decel Time 2]
Thisread/writeparameter setsthedecelerationtime for parameters68 to
71 (preset RPM 4-7).
0x2A-1-
170
100 to
65500
1ms 20000 ms
73 AC Drive
Extension
[Decel Time 2]
This read/write parameter sets the deceleration time.
0xB3-1-70 10 to 60000 1 ms 20000 ms
This parameter applies only to the Analog Signal Follower model.
This parameter applies only to the Preset Speed model.