User guide
60
D35 and D36 With Keypad or Comm Control Options
SEE TABLE 2
PILOT DEVICE
SEE TABLE 2
PILOT DEVICE
*
REMOTE LOCAL
(OX)
DEVICE
2-WIRE
DEVICE
2-WIRE
*
REMOTE LOCAL
(OX)
*
*
25
25
10
11
9
8
7
6
4
5
3
TB3
1
2
11
10
9
8
7
6
TB3
5
4
2
3
1
01
12-17-99 ARS
99P0562
C-300358-2
WS\STD\300358\02-13
13
14
SCHEMATIC, BULLETIN 160 AC DRIVE SERIES C
CONTROL LOGIC OPTION D35 & 36 WITH
KEYPAD OR COMMUNICATION CONTROL OPTIONS
24VDC INPUT INTERFACE
ACAD
12-17-99
ARS
12-17-99
ARS
12-17-99
L\DM\1336P??
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
A
B
C
D
E
F
G
H
40
41
39
38
37
36
35
28
33
34
32
31
30
29
27
26
25
24
23
22
14
20
19
18
17
16
15
13
12
11
9
10
8
7
6
5
4
2
3
1
21
28
31
30
29
27
26
25
24
23
22
14
20
19
18
17
16
15
13
12
11
9
10
8
7
6
5
4
2
3
1
32
INDEX NO.
REFERENCE DWG.
DATE
APP'D
DATE
DATE
DR.
TITLE:
DWG.
NO.
REV. DATE
ECN NUMBER
LEAD ENG.
SH:
SH:
NEXT
BY
THIS DRAWING IS THE PROPERTY OF
ROCKWELL AUTOMATION, INC. OR ITS
SUBSIDIARIES AND MAY NOT BE COPIED,
USED OR DISCLOSED FOR ANY PURPOSE
EXCEPT AS AUTHORIZED IN WRITING BY
ROCKWELL AUTOMATION, INC.
CUST.
SUPPLIED
120VAC
120VAC
SUPPLIED
CUST.
OPTION
D35
D36
SYMBOL
PL4
PL3
COLOR
RED
WHITE
LEGEND
DRIVE FAULT
DRIVE RUN
PAR 47 SETTING
0 (DEFAULT)
2
TABLE 2
LAMINATED DRAWING MUST BE RE-ISSUED TO SHOP AFTER ECN
(X2) (X1)
(X2) (X1)
24VDC
INTERFACE
INTERFACE
24VDC
AND PROTECTED 24VDC
+
CUSTOMER SUPPLIED
-
AND PROTECTED 24VDC
+
CUSTOMER SUPPLIED
-
ANALOG SIGNAL FOLLOWER
4-20mA INPUT
RUN REVERSE
CONTROL BOARD
TERMINAL BLOCK TB3
WIPER/0-10VDC INPUT
TB3/KEYPAD OR COMMUNICATION CONTROL
RUN FORWARD
PROGRAMMABLE RELAY
OUTPUTS
6
11
10
9
COMMON
8
7
TB3
5
4
+10V POT
COMMON
2
3
1
(PAR 46 = 6)
INPUT MODE 6
160
RUN REVERSE
RUN FORWARD
CONTROL BOARD
PRESET SPEED MODEL
TERMINAL BLOCK TB3
OUTPUTS
PROGRAMMABLE RELAY
TB3/KEYPAD OR COMMUNICATION CONTROL
10
11
9
8
COMMON7
6
COMMON
SW34
5
3
SW1
TB3
SW2
1
2
INPUT MODE 6
(PAR 46 = 6)
160
R
R
CONNECT THE -24VDC & +24VDC TO TERMINALS TB3-7 & TB3-8 RESPECTIVELY WHEN
NOTE 1:
D13, D33 OR MX12 ARE NOT ORDERED.
NOTE 2:
NOTE 2:
NOTE 2: CONNECT TERMINAL 7 TO ENCLOSURE GROUND WHEN EMC OPTION IS PRESENT.