Owner's manual

Chapter 2 –Installation and Wiring
2-9
Control Wiring (continued)
Figure 2.8 – TB3 Two Wire “Accel/Decel” control
(Setting 4)
8
7
6
5
Run Reverse
Run Forward
Common
Accel/decel
select
Signal
Specification
Contact Closure Input
Used to select Accel/Decel.
TerminalTB3
Shielded Wire
Contact Closure Input
Contact Closure Input
Common
Refer to Figure 2.11.
Figure 2.9 – TB3 Two Wire “Enable” control
(Setting 5)
Specification
8
7
6
5
Run Reverse
Run Forward
Enable
Common
Signal
Contact Closure Input required
to operate controller
Common
TerminalTB3
Shielded Wire
Contact Closure Input
Contact Closure Input
Refer to Figure 2.11.
Figure 2.10 – TB3 Two Wire “Local/Remote” control
(Setting 6)
Specification
8
7
6
5
Run Reverse
Run Forward
Local/
Remote
Common
Signal
Contact Closure Input
Used to select local (TB3)
Control.
Common
Contact Closure Input
TerminalTB3
Shielded Wire
Contact Closure Input
Refer to Figure 2.11.
Figure 2.11
Input Mode
Setting
TB3-8
Open
TB3-8
Closed
4
Accel 2
Decel 2
Accel 1
Decel 1
5
Controller
Disabled
Controller
Enabled
6
Local (TB3)
Control
Remote
Control
The “Run” input must be a maintained input. After a stop
command, either a “Run Forward” or “Run Reverse” input must
be toggled to start the controller.
When this input is in an open state, P69 – [Accel Time 2] and
P70 – [Decel Time 2] are active.
When this input in in an open state, all power is removed from
the motor and it will “coast to rest”.
When this input is in an open state the Frequency source is
always from the terminal block regardless of the setting of
P59 – [Frequency Select].
Important: In modes 4 through 6, Terminal
TB3-8 is also used to clear faults. See Figure 2.12
for details.
Important: The system programmer is
responsible for returning terminal TB3-8 to its
original state if necessary.
Figure 2.12
TB3-8
CLOSED
TB3-8
OPEN
Fault
occurs
Fault
clears
Fault
clears
Fault
occurs