Owner's manual
Chapter 2 –Installation and Wiring
2-5
Table 2.G – Cable Length Recommendations — Capacitive Current
380 460V
Motor Cable Only RWR at Drive
①
Reactor at Motor
380 – 460V
Ratings
kHz
Shielded
②
Unshielded Shielded
②
Unshielded Shielded
②
Unshielded
Ratings
kz
ft. m. ft. m. ft. m. ft. m. ft. m. ft. m.
22kW
2 360 110 750 229 280 85 600 183 410 125 525 160
2.2 kW
(3 HP
4 335 102 600 183 260 79 600 183 370 113 475 145
(3
HP
8 300 91 410 125
➀ ➀ ➀ ➀
310 94 420 128
15kW
2 300 91 540 165 430 131 540 165 310 94 425 130
1.5 kW
(2 HP
4 300 91 425 130 410 125 425 130 300 91 400 122
(2
HP
8 300 91 300 91
➀ ➀ ➀ ➀
300 91 350 107
075kW
2 300 91 375 114 250 76 375 114 300 91 300 91
0.75 kW
(1 HP)
4 300 91 300 91 225 69 375 114 300 91 300 91
(1
HP)
8 300 91 300 91
➀ ➀ ➀ ➀
300 91 300 91
055kW
2 300 91 375 114 250 76 375 114 300 91 300 91
0.55 kW
(0 75 HP)
4 300 91 310 94 225 69 375 114 300 91 300 91
(0
.
75
HP)
8 300 91 300 91
➀ ➀ ➀ ➀
300 91 300 91
037kW
2 300 91 375 114 250 76 375 114 300 91 300 91
0.37 kW
(0 5 HP)
4 300 91 325 99 225 69 375 114 300 91 300 91
(0
.
5
HP)
8 300 91 300 91
➀ ➀ ➀ ➀
300 91 300 91
200 240V
Motor Cable Only RWR at Drive Reactor at Motor
200 – 240V
Ratings
Shielded Unshielded Shielded Unshielded Shielded Unshielded
Ratings
ft. m. ft. m. ft. m. ft. m. ft. m. ft. m.
0.37 to 2.2 kW
(0.5 to 3 HP)
2 thru 8 kHz
500 152 800 244 ③ ③ ③ ③ 500 152 800 244
➀ Not recommended for use above 4 kHz PWM frequency.
➁ When using shielded cable at lightly loaded conditions, the 0.75 Kw (1 Hp) and below cable length recommendations are 61m (200 ft.)
➂ Not recommended for 230V applications.