Diagnostics 7-3
1560E-UM050B-EN-P - June 2013
Fault Codes
Table 7.A provides a complete cross-reference of the available fault codes
and corresponding fault descriptions.
Table 7.A
Fault Code Cross-Reference
Fault Code Fault Code
Line Loss A 1 Underload 23
Line Loss B 2 Jam 24
Line Loss C 3 Stall 25
Shorted SCR A 4 Phase Reversal 26
Shorted SCR B 5 Coms Loss P2 27
Shorted SCR C 6 Coms Loss P3 28
Open Gate A 7 Coms Loss P5 29
Open Gate B 8 Network P2 30
Open Gate C 9 Network P3 31
PTC Pwr Pole 10 Network P5 32
SCR Overtemp Ê 11 Ground Fault 33
Motor PTC 12 Excess Starts/Hour 34
Open Bypass A 13 Power Loss A 35
Open Bypass B 14 Power Loss B 36
Open Bypass C 15 Power Loss C 37
No Load A 16 Hall ID 38
No Load B 17 NVS Error 39
No Load C 18 No Load 40
Line Imbalance 19 Line Loss A 41
Overvoltage 20 Line Loss B 42
Undervoltage 21 Line Loss C 43
Overload 22
Ê Not applicable in MV applications.
Fault Contact The auxiliary contact is located at terminals 29 and 30. Note that the state
this contact takes upon power-up (normally open or normally closed) can be
programmed. These parameters can be found in either Basic Setup or the
Linear List groups when modifying parameters in the Set Up mode.