PARAMETER AND VARIABLE DESCRIPTIONS 6-23
1557-UM050F-EN-P June 2013
Line Overvoltage Trip [Line O/V trip]
Linear number: 165
Minimum value: 0.00 pu
Maximum value: 1.50 pu
Default value: 1.20 pu
This parameter specifies the level the line voltage must exceed before a line overvoltage fault is indicated.
Line Overvoltage Delay [Line O/V delay]
Linear number: 166
Minimum value: 0.000 sec
Maximum value: 10.000 sec
Default value: 0.050 sec
This parameter specifies the time the line voltage must remain above the trip level before a line
overvoltage fault is indicated.
Line Undervoltage Trip [Line U/V trip]
Linear number: 167
Minimum value: 0.70 pu
Maximum value: 1.50 pu
Default value: 0.85 pu
This parameter specifies the level the line voltage must fall below before a line undervoltage condition is
indicated.
Line Undervoltage Delay [Line U/V delay]
Linear number: 168
Minimum value: 0.010 sec
Maximum value: 0.040 sec
Default value: 0.020 sec
This parameter specifies the time the line voltage must remain below the trip level before a line
undervoltage condition is indicated.
DC Link Overcurrent Trip [DC O/C trip]
Linear number: 169
Minimum value: 0.10 pu
Maximum value: 2.00 pu
Default value: 2.00 pu
This parameter specifies the level the dc link current must exceed before a dc link overcurrent fault is indicated.
NOTE: For current ratings near the maximum for the drive frame size, this parameter will be automatically
limited to a maximum value less than 2.00. This feature was added in Rev 4.60/5.10.
DC Link Overcurrent Delay [DC O/C delay]
Linear number: 170
Minimum value: 0.000 sec
Maximum value: 0.040 sec
Default value: 0.004 sec
This parameter specifies the time the dc link current must remain above the trip level before a dc link
overcurrent fault is indicated.
NOTE: For Bulletin 1557M Drives, this parameter is internally limited to 0.004 sec maximum.
Ground Fault Overcurrent Trip [Gnd flt O/C trip]
Linear number: 171
Minimum value: 0.0 A
Maximum value: 1.0 A
Default value: 0.5 A
This parameter specifies the level the ground fault current signal must exceed before a ground fault overcurrent
is indicated.