Owner's manual
DESCRIPTION OF OPERATION 5-25
1557-UM050F-EN-P –June 2013
Motor O/C trip
(P177)
I stator
(V340)
TIME
DELAY
Motor O/C delay
(P178)
Motor overcurrent
Fault Flags 1M bit 4
(V370)
Motor O/V trip
(P181)
TIME
DELAY
Motor O/V delay
(P182)
Motor overvoltage
Fault Flags 1M bit 6
(V370)
V stator
(V344)
Motor O/C trip
(P177)
I DC
TIME
DELAY
Motor O/C delay
(P178)
Mtr h/w o/c
Fault Flags 1M bit 5
(V370)
DC O/V trip
(P187)
TIME
DELAY
DC O/V delay
(P188)
Mtr dc overvoltage
Fault Flags 1M bit 7
(V370)
V DC
Gnd flt O/V
trip
(P169)
TIME
DELAY
Gnd flt O/V
delay
(P190)
Neutral overvoltage
Fault flags 2 bit 5
(V371)
V neutral
motor
(V347)
Motor O/S
trip
(P165)
TIME
DELAY
Motor O/S
delay
(P156)
Mtr overspeed
Fault flags 2 bit 2
(V371)
Speed
feedback
(V259)
HARDWARE SOFTWARE
TRIP
LEVEL
CALC
1.04 pu
-
Motor O/L trip
(P179)
Motor O/L delay
(P180)
0.5
Motor overload
Fault flage 2 bit 1
(V371)
Motor overload waring
Warning flags bit 1
(V373)
INTEGRATOR
I stator
(V340)
Machine Converter Protection