Owner's manual

DESCRIPTION OF OPERATION 5-23
1557-UM050F-EN-P June 2013
Line O/C trip
(P161)
Idc feedback
(V322)
TIME
DELAY
Line O/C
delay
(P162)
Line overcurrent
Fault Flags 1L bit 4
(V369)
V Line
(V324)
Line O/V trip
(P165)
TIME
DELAY
Line O/V
delay
(P166)
Line overvoltage
Fault Flags 1L bit 6
(V369)
TIME
DELAY
Line U/V delay
(P168)
Line Uvervoltage
Warning Flags
bit 2 (V373)
Line U/V trip
(P167)
DC O/C trip
(P169)
IDC
TIME
DELAY
DC O/C delay
(P170)
Line h/w o/c
Fault Flags 1L bit 5
(V369)
Line DC O/V trip
(P173)
VDC
TIME
DELAY
Line DC O/V delay
(P174)
Line dc overvoltage
Fault Flags 1L bit 7
(V369)
Gnd flt O/C
trip
(P171)
TIME
DELAY
Gnd flt O/C
delay
(P172)
Ground fault
Fault Flags 1L bit 9
(V371)
A/D
Analog input 2L
(V354)
Line
Converter
A12
TRIP
LEVEL
CALC
Idc feedback
(V322)
1.10
1.04 pu
-
Line O/L trip
(P163)
Line O/L delay
(P164)
0.5
Line overload
Fault flags 2 bit 0
(V371)
Line overload warning
Warning flags bit 0
(V373)
HARDWARE SOFTWARE
INTEGRATOR
Line Converter Protection