User guide
4-8 Common Installation
1512A-UM102B-EN-P – Ju ne 2013
L1 L3L2 GRD
MTR
ISOLATING SWIT CH
DOOR INTERLOC K
CURR ENT LIMITING
POWER FUSES
TEST SUPP LY POINT
X
X
PRIMARY FUSES
CURR ENT LIMITING
V
VA
V
OVERLOAD
592
RE MOTE EQUIPMENT
"IEEE" NUMBER FOR PROTECTIVE DEVICE
LOW VOLTAGE DOOR MOUNT ED DEVICE
D
CUSTOMER WIRING
LEGE ND
2400V-6900V,3Ø, 50/60Hz
RE MOVE JUMPER WHEN CONNECT ING RE MOTE EQUIPMENT
EXTRA AUXILIARY
CON TACTS
MOV
32
1
EC
-
+
4
TCO
12
11
AUX CCO
5
6
L1
G
+ -
V
V
STOP
DSTART
D
V
D
D
RUN
OFF
MAIN
CON TACTOR (M)
37
K M L
36
3332
3534
1
I JM
31
M F
30
E
1
OL
4
M-IV
15 16
CON TACT OR
STATUS
321A
14
M-IV
9 10
CLO SE
12
14A
F7
2.0A
171315
20
A BM
M-IV
M
M
N C
1
12
(1) (2)
(3) (4)
NOR MAL
OFF
TEST
X
X
47
46
44
42
OL
49
TS
F3
__EF2__EF2
____
120
500
CPT1
M
(6) (5)
(7) (8)
12
ISa
5
IS
T2
T1
CT2
CT1
T3
CT3
11
6
10
F1
F1
F1
78
9
ISb
50/60Hz120 V
HMG
INTELLIVAC TO BE PROGRAMMED/C ONF IGURED BY THE
POWER APPLIED. THE FOLLOW ING FACTO RY INSTA LLED
OUTPUT RELAY CONTACT S SHOWN WITHOUT CONTR OL
MODULE STATUS - FAIL SAFE
CONT ACTOR STATUS - FAIL SAFE
CUSTOMER BEFORE START-U P.
CONF IGURATION/ POWER-UP STATES ARE IN EFFE CT:
INTELLIVAC NO TES:V
- INTELLIVAC MODULE VACUUM CONTACTO R AUX ILIARY INPUTAUX
- INTELLIVAC MODULE EXTERNAL CAPACITOR INPUTEC
- INTELLIVAC MODULE CLOSING C OIL OUT PUTCCO
- MAIN CONTACTO R INT ELLIVAC MODUL EM-IV
- INTELLIVAC MODULE TRIP COIL OUTPUTTCO
Figure 4.5 – Typical Wiring Diagram: Electrically Held Vacuum Contactor (with IntelliVAC Control)