Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013 71
ArcShield Unit Information Appendix A
Figure 68 - Chimney Exhaust Space Requirements
Minimum H1: 1.7 m (67 in.)
Minimum H: 1 m (39 in.)
Additional Notes
The walls of the plenum exit area must be capable of withstanding the
pressure generated.
Any painted surfaces which face direct contact with the arc products may
ignite. Flame suppression is recommended.
The exit point can also be outside the building. Ensure exit area can not be
blocked by ice, snow, or vermin nests.
Access barriers are recommended as a means of restricting access by
personnel while the equipment is energized. Chain link fencing is a
suitable barrier material.
Equipment that consists of more than 4 vertical sections bolted together
may require additional plenum exits. Rockwell Automation will provide
guidance on requirements for additional plenum exits when required.
H1
H