32 Rockwell Automation Publication 1512A-UM100F-EN-P - May 2013
Chapter 4 Common Installation
2. Connect the incoming power lines to the power bus. Torque to
specifications (refer to Recommended Torque Values
on page 2 of
Chapter 1) (see Figure 37).
Figure 37 - Incoming Line Cable Connections
3. Connect the ground wire to the ground bus lug.
4. Connect any external control wires to the control panel terminal blocks in
the low voltage compartment. Refer to wiring diagram.
Power
Cable
Lugs
Ground
Bus
Lug
IMPORTANT
If line cables require installation by front access, complete the incoming line
connection before installing load cables.