Wiring (MC) 6-3
1503-UM054C-EN-P June 2013
Figure 6.2 Wiring Diagram for Full Voltage Reversing
Configuration Required:
Gate #34 Off Delay Timer Reverse Contactor
Gate #32 Off Delay Timer Forward Contactor
Gates # 32 and 34 are the close command disable timers for the respective contactors,
typic ally these timers are set to an equal value.
The purpose of these timers is to allow a motor turning in the forward direction a pre
determined amount of time to come to a stop before the reverse contactor can be closed
and vice versa. Preset Value: 10 Seconds