Figure 6.2 – Wiring Diagram for Full Voltage Reversing
Configuration Required:
• Gate #34 Off Delay Timer Reverse Contactor
• Gate #32 Off Delay Timer Forward Contactor
Gates # 32 and 34 are the close command disable timers for the respective contactors,
typic ally these timers are set to an equal value.
The purpose of these timers is to allow a motor turning in the forward direction a pre
determined amount of time to come to a stop before the reverse contactor can be closed
and vice versa. Preset Value: 10 Seconds