Manual

Description of Features 4-13
1503-UM054C-EN-P June 2013
Supply Voltages The AC and DC supply voltage measurements represent the RMS
values of the input mains for each of the IntelliVAC Plus/MC
modules. The voltage values for each of the five (5) IB units, shall
be made available on DeviceNet in the following manner:
IB1 Line Voltage = ‘xxx.xx’V
IB2 Line Voltage = ‘xxx.xx’V
IB3 Line Voltage = ‘xxx.xx’V
IB4 Line Voltage = ‘xxx.xx’V
IB5 Line Voltage = ‘xxx.xx’V
I B1 DC Bus Voltage = ‘xxx.xx’V
IB2 DC Bus Voltage = ‘xxx.xx’V
IB3 DC Bus Voltage = ‘xxx.xx’V
IB4 DC Bus Voltage = ‘xxx.xx’V
IB5 DC Bus Voltage = ‘xxx.xx’V
If the input voltage is too high, too low or missing, then the
following messages will be made available on DeviceNet:
I B1 Line Undervoltage Close’ (Line voltage1 < 95Vrms)
IB2 Line Undervoltage Close’ (Line voltage2 < 95Vrms)
IB3 Line Undervoltage Close’ (Line voltage3 < 95Vrms)
IB4 Line Undervoltage Close’ (Line voltage4 < 95Vrms)
IB5 Line Undervoltage Close’ (Line voltage5 < 95Vrms)
IB1 Line Undervoltage Hold’ (Line voltage1 < 80Vrms)
IB2 Line Undervoltage Hold’ (Line voltage2 < 80Vrms)
IB3 Line Undervoltage Hold’ (Line voltage3 < 80Vrms)
IB4 Line Undervoltage Hold’ (Line voltage4 < 80Vrms)
IB5 Line Undervoltage Hold’ (Line voltage5 < 80Vrms)
IB1 Line Overvoltage’ (Line voltage1 > 265Vrms)
IB2 Line Overvoltage’ (Line voltage2 > 265Vrms)
IB3 Line Overvoltage’ (Line voltage3 > 265Vrms)
IB4 Line Overvoltage’ (Line voltage4 > 265Vrms)
IB5 Line Overvoltage’ (Line voltage5 > 265Vrms)
I B1 Line Loss (Line voltage1 < 50Vrms); electronics, only,
function in this range
I B2 Line Loss (Line voltage2 < 50Vrms); electronics, only,
function in this range
I B3 Line Loss (Line voltage3 < 50Vrms); electronics, only,
function in this range
I B4 Line Loss (Line voltage4 < 50Vrms); electronics, only,
function in this range
I B5 Line Loss (Line voltage5 < 50Vrms); electronics, only,
function in this range