E-14 DeviceNet Information
1503-UM054C-EN-P – June 2013
Table E.25 - Instance Attribute (cont.)
Parameter
No.
Control Parameter
Access
Rule
Type Description NV CCV
58
TDUV base Time (from DIP)*
Get
USINT
0.2/0.5/1.0/2.0
N
N
59
Line Undervoltage Hold
Get
BOOL
0=not present
1=present
N
N
60
Contactor Long Drop Out Time
Get
BOOL
0=not present
1=present
N
N
61
Coil Current trend***
Get
LONG INT*
0~xx.xxx A
N
N
62
IB module status****
Get/Set
UINT
N
N
63
Correct MC Termination
resistor@ Ibx Termination
resistor
Get
BOOL
0=not present
1=present
N
N
64
IB revision
Get
LONG INT*
XX.XX
N
N
Note*: In EDS its decimal position is 2, scaling to engineering unit,
i.e, the data 100 will be scale to 1.00 in RSNetWorx parameter page.
Note**: These parameters keep the 3 latest events
Note***: The current trend is for electrically held contactor only,
which provide a way for the IntelliCENTER software to display the
current trend of contactor’s close transition state, this parameter will
not be displayed in RSNetWorx’ parameter page.
Note****: Some bits are set to clear fault/warning.
Note: For IB1 this is correct MC termination resistor, for IB 2~5 this
is IBx termination resistor.
Table E.26 - Common Services
Service
Code
Implementation for
Service Name
Class
Instance
0E hex
Yes
Yes
Get_Attribute_Single
10 hex No Yes Set_Attribute_Single
18hex No Yes Get_Member*
Note*: Only used for get the event log member.