B-180 Parameters
1503-UM054C-EN-P June 2013
Termination Resistor Installed in IB5
[IB5 Termination Resistor]
Parameter Number: 344,_,_,_,_.
Access rule: Get
Data Type: BOOL
Object Mapping: 0x384-5-63
Group: Diagnostics
Units : -
Minimum Value: 0 = Not Present
Maximum Value: 1 = Present
Default Value: 0
This parameter allows the user to view the status of the MC Termination
Res is tor installation on IB5. If this bit is0’, then the MC Termination
Resistor is not installed on the IB5 unit. If this bit is1’, then the MC
Termination Resistor is installed on the IB5 unit. For the MC system to
have the correct Termination Resistor installed, only the las t MC unit in
the MC system must have its resistor turned on.
Status Word for the IE [IE Status Word]
Parameter Number: 345,284,223,162,100.
Access rule: Get/Set
Data Type: WORD
Object Mapping: 0xB4-1-128
Group: Diagnostics
Units: -
Minimum Value: 0
Maximum Value: 0xFFFF
Default Value: 0
This parameter allows the user to view the IE Status Word. If a bit is
‘0then the fault or warning is not present. If a bit is a 1’ then the
fault or warning is present. See Table 4.F and Table 4.J in Chapter 4
for a detailed description of each of the IE Status Word bits.
Table B.44 Status Word for IE
Bit Enum Text Description
0
System locked
System locked due to repeated fault
1
Line under-voltage
Line under-voltage
2
Line over-voltage
Line over-voltage
3
Altitude setting warning
Altitude settings inconsistent in MC system
4
RTC failure
RTC failure
5
DNet power loss
DeviceNet power loss
6
IB5 not responding
IB5 not responding on RS485
7
IB4 not responding
IB4 not responding on RS485
8
IB3 not responding
IB3 not responding on RS485
9
IB2 not responding
IB2 not responding on RS485
10
IB1 not responding
IB1 not responding on RS485
11
unused
unused
12
RS485 incorrect address
RS485 incorrect address
13
RS485 communication fault
RS485 communication fault
14
unused
unused
15
unused
unused