Manual
B-176 Parameters
1503-UM054C-EN-P – June 2013
Status Word for IB4 [IB 4 Status Word]
Parameter Number: 338,279,_,_,_.
Access rule: Get
Data Type: WORD
Object Mapping: 0x384-4-62
Group: Diagnostics
Units : -
Minimum Value: 0
Maximum Value: 0xFFFF
Default Value: 0
This parameter allows the user to view the IB4 Status Word. If a bit
is ‘0’ then the fault or warning is not present. If a bit is a ‘1’ then the
fault or warning is present.
Table B.42 – Status Word for IB4
Bit Enum Text Description
0
Bit 0: unused
unused
1
Bit 1: unused unused
2
Bit 2: unused
unused
3
Bit 3: Power Up with Contactors Closed
Power Up w ith Contactor Closed IB4
4
Bit 4: Open Coil Open
Trip Coil Open on IB4
5
Bit 5: Close Coil Open
Close Coil Open on IB4
6
Bit 6: Power Up with Invalid DIPs
Power Up w ith Invalid DIPs on IB4
7 Bit 7: MC Malfunction MC Malfunction on IB4
8
Bit 8: Drop Out During Hold Drop Out During Hold on IB4
9
Bit 9: Contactor Fails to Drop Out
Contactor Fails to Drop Out on IB4
10
Bit 10: Power Up with Close Command
Power Up w ith Close Command on IB4
11
Bit 11: Long Close Time
Long Close Time on IB4
12
Bit 12: Underv oltage w ith Close Command Present
Undervoltage with Close Command Present on IB4
13
Bit 13: Long Drop Out Time
Long Drop Out Time on IB4
14 Bit 14: Mechanical Latch Trip Fail Mechanical Latch Trip Fail on IB4
15
Bit 15: Invalid Command Invalid Command on IB4