Manual

Parameters B-175
1503-UM054C-EN-P June 2013
Status Word for IB3 [IB 3 Status Word]
Parameter Number: 337,278,219,_,_.
Access rule: Get
Data Type: WORD
Object Mapping: 0x384-3-62
Group: Diagnostics
Units : -
Minimum Value: 0
Maximum Value: 0xFFFF
Default Value: 0
This parameter allows the user to view the IB3 Status Word. If a bit
is 0’ then the fault or warning is not present. If a bit is a ‘1’ then the
fault or warning is present.
Table B.41 Status Word for IB3
Bit Enum Text Description
0
Bit 0: unused
unused
1
Bit 1: unused
unused
2 Bit 2: unused unused
3
Bit 3: Power Up with Contactors Closed Power Up w ith Contactor Closed IB3
4
Bit 4: Open Coil Open
Trip Coil Open on IB3
5
Bit 5: Close Coil Open
Close Coil Open on IB3
6
Bit 6: Power Up with Invalid DIPs
Power Up w ith Invalid DIPs on IB3
7
Bit 7: MC Malfunction
MC Malfunction on IB3
8
Bit 8: Drop Out During Hold
Drop Out During Hold on IB3
9
Bit 9: Contactor Fails to Drop Out
Contactor Fails to Drop Out on IB3
10
Bit 10: Power Up with Close Command Power Up with Close Command on IB3
11
Bit 11: Long Close Time
Long Close Time on IB3
12
Bit 12: Underv oltage w ith Close Command Present
Undervoltage with Close Command Present on IB3
13
Bit 13: Long Drop Out Time
Long Drop Out Time on IB3
14
Bit 14: Mechanical Latch Trip Fail
Mechanical Latch Trip Fail on IB3
15 Bit 15: Invalid Command Invalid Command on IB3