Manual

B-174 Parameters
1503-UM054C-EN-P June 2013
Status Word for IB2 [IB 2 Status Word]
Parameter Number: 336,277,218,159,_.
Access rule: Get
Data Type: WORD
Object Mapping: 0x384-2-62
Group: Diagnostics
Units : -
Minimum Value: 0
Maximum Value: 0xFFFF
Default Value: 0
This parameter allows the user to view the IB2 Status Word. If a bit
is 0’ then the fault or warning is not present. If a bit is a ‘1’ then the
fault or warning is present.
Table B.40 Status Word for IB2
Bit Enum Text Description
0
Bit 0: unused
unused
1
Bit 1: unused unused
2
Bit 2: unused
unused
3
Bit 3: Power Up with Contactors Closed
Power Up w ith Contactor Closed IB2
4
Bit 4: Open Coil Open
Trip Coil Open on IB2
5
Bit 5: Close Coil Open
Close Coil Open on IB2
6
Bit 6: Power Up with Invalid DIPs
Power Up w ith Invalid DIPs on IB2
7 Bit 7: MC Malfunction MC Malfunction on IB2
8
Bit 8: Drop Out During Hold Drop Out During Hold on IB2
9
Bit 9: Contactor Fails to Drop Out
Contactor Fails to Drop Out on IB2
10
Bit 10: Power Up with Close Command
Power Up w ith Close Command on IB2
11
Bit 11: Long Close Time
Long Close Time on IB2
12
Bit 12: Underv oltage w ith Close Command Present
Undervoltage with Close Command Present on IB2
13
Bit 13: Long Drop Out Time
Long Drop Out Time on IB2
14 Bit 14: Mechanical Latch Trip Fail Mechanical Latch Trip Fail on IB2
15
Bit 15: Invalid Command Invalid Command on IB2