Parameters B-167
1503-UM054C-EN-P – June 2013
Module Status of IB1 [IB Status]
Parameter Number: 323,265,207,149,90.
Access rule: Get
Data Type: BYT E
Object Mapping: 0xB4-1-120
Group: Diagnostics
Units : -
Minimum Value: 0
Maximum Value: 0xFF
Default Value: 0
This parameter allows the user to view the Module Status of IB1.
Table B.38 – Module Status of IB1
Bit Enum Text Description
0
Bit 0: Test Mode
IB1 in Test Mode
1
Bit 1: Normal Mode
IB1 in Normal Mode
2
Bit 2: Local Mode
IB1 in Local Mode
3
Bit 3: Remote Mode IB1 in Remote Mode
4
Bit 4: Isolation SW IB1 Isolation SW
5
Bit 5: Speed REV
IB1 in REV Speed
6
Bit 6: Speed FWD
IB1 in FWD Speed
7
Bit 7: Protection
IB1 in Protection Mode
See “Status Inputs” in DeviceLogix, Chapter 9 for an explanation of
each of those bits.
Run the DeviceLogix Module [Run DeviceLogix]
Parameter Number: 324,266,208,150,91.
Access rule: Get/Set
Data Type: BOOL
Object Mapping: 0x30E-1-1
Group: Diagnostics
Units : -
Minimum Value: 0 = Stop DeviceLogix Program
Maximum Value: 1 = Run DeviceLogix Program
Default Value: 0
This parameter allows the user to view and set the operating mode
for the DeviceLogix Module that has been selected. If the bit is a
‘0’ then the selected DeviceLogix Program will be Stopped. If the
bit is a ‘1’ then the selected DeviceLogix Program will be Run.