Manual

Description of Features 4-7
1503-UM054C-EN-P June 2013
IB3 Delay Restart Wait Time = ‘ ‘x Sec
(Note: This value, as it is being viewed, will be constantly
updated as the wait time decreases.)
IB4 Delay Restart Wait Time = ‘ ‘x Sec
(Note: This value, as it is being viewed, will be constantly
updated as the wait time decreases.)
IB5 Delay Restart Wait Time = ‘ ‘x Sec
(Note: This value, as it is being viewed, will be constantly
updated as the wait time decreases.)
Temporary Jog Function
It shall be possible to connect the “Open” input to function as a
“Temporary Jog” (for electrically held contactors only). Thus, this
feature shall be permitted when an electrically held contactor is selected.
It shall be possible to Jog a motor under the following conditions:
Maximum of 30 sec. continuously
No more than “x” sec. of Jog activity during “y” seconds (to be
determined by testing)
This value should be programmable for the IE unit with the Jog time
“x” being from 0 to 30 seconds in 1 second increments and the
repetition time “y” being from 0 to 60 seconds in 1 second
increments.
The Temporary Jog parameters will be available, for each of the five
(5) IB units, on DeviceNet in the following manner:
IB1 Jog Time = ‘0 Sec to ’30 Sec in 1 second increments
IB2 Jog Time = ‘0 Sec to ’30 Sec in 1 second increments
IB3 Jog Time =0 Sec to ’30 Sec in 1 second increments
IB4 Jog Time = ‘0 Sec to ’30 Sec in 1 second increments
IB5 Jog Time = ‘0 Sec to ’30 Sec in 1 second increments
IB1 Jog Repetition Time = 0 Sec to ’60 Sec in 1 second
increments
IB2 Jog Repetition Time = 0 Sec to ’60 Sec in 1 second
increments
IB3 Jog Repetition Time = 0 Sec to ’60 Sec in 1 second
increments
IB4 Jog Repetition Time = 0 Sec to ’60 Sec in 1 second
increments
IB5 Jog Repetition Time = 0 Sec to ’60 Sec in 1 second
increments