Parameters B-81
1503-UM054C-EN-P – June 2013
Jog Time for IB1 [IB 1 Jog Time]
Parameter Number: 148,125,102,79,55.
Access rule: Get/Set
Data Type: USINT
Object Mapping: 0x384-1-21
Group: Configuration
Units : Seconds
Minimum Value: 0
Maximum Value: 30
Default Value: 12
This parameter allows the user to view and set the Jog Time for
contactor IB1. It indicates the amount of time that a contactor can be
Jogged (momentarily closed) for. This is only for Electric ally Held
contactors and makes use of the Open command. See Temporary
Jog Function in Chapter 4 for a more detailed description of this
feature.
Jog Time for IB2 [IB 2 Jog Time]
Parameter Number: 149,126,103,80,_.
Access rule: Get/Set
Data Type: USINT
Object Mapping: 0x384-2-21
Group: Configuration
Units : Seconds
Minimum Value: 0
Maximum Value: 30
Default Value: 12
This parameter allows the user to view and set the Jog Time for
contactor IB2. It indicates the amount of time that a contactor can be
Jogged (momentarily closed) for. This is only for Electrically Held
contactors and makes use of the Open command. See Temporary
Jog Function in Chapter 4 for a more detailed description of this
feature.