B-78 Parameters
1503-UM054C-EN-P – June 2013
Delay Restart Time for IB5
[IB 5 Delay Restart Time]
Parameter Number: 142,_,_,_,_.
Access rule: Get/Set
Data Type: UINT
Object Mapping: 0x384-5-19
Group: Configuration
Units : Seconds
Minimum Value: 6
Maximum Value: 3600
Default Value: 12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB5. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.
Delay Restart Wait Time for IB1
[IB 1 Delay Restart Wait Time]
Parameter Number: 143,121,99,77,54.
Access rule: Get
Data Type: UINT
Object Mapping: 0x384-1-20
Group: Configuration
Units : Seconds
Minimum Value: 0
Maximum Value: 3600
Default Value: 0
This parameter allows the user to view the Delay Restart Wait Time
for IB1. It shows the time left, as a constantly updated real time,
after the contactor has closed, before it is permitted to close again.
This parameter works in conjunction with parameter #138 which
defines the minimum time allowed between successive closings of
contactor IB1. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.