Manual

Parameters B-77
1503-UM054C-EN-P June 2013
Delay Restart Time for IB3
[IB 3 Delay Restart Time]
Parameter Number: 140,119,98,_,_.
Access rule: Get/Set
Data Type: UINT
Object Mapping: 0x384-3-19
Group: Configuration
Units : Seconds
Minimum Value: 6
Maximum Value: 3600
Default Value: 12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB3. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.
Delay Restart Time for IB4
[IB 4 Delay Restart Time]
Parameter Number: 141,120,_,_,_.
Access rule: Get/Set
Data Type: UINT
Object Mapping: 0x384-4-19
Group: Configuration
Units : Seconds
Minimum Value: 6
Maximum Value: 3600
Default Value: 12
This parameter allows the user to view and set the Delay Restart
Time between successive Open/Trip and Close commands for
contactor IB4. This sets a maximum repetition time for the cycling
of the contactor. It can also be used to prevent rapid restating of the
motor. See Delayed Restart in Chapter 4 for a more detailed
description of this feature.