Parameters B-69
1503-UM054C-EN-P – June 2013
Contactor Pick Up Time for IB3
[IB 3 Pick Up Time]
Parameter Number: 125,107,89,_,_.
Access rule: Get
Data Type: USINT
Objec t Mapping: 0x384-3-18
Group: Configuration
Units : mSeconds
Minimum Value: 0
Maximum Value: 255
Default Value: 0
This parameter allows the user to view the Pick Up Time for the IB3
contactor. The Pick Up Time is the interval from when a Close or
Trip command is issued to the time that the Contactor Auxiliary
contact on IB3 opens, indicating that the contactor is closed.
Contactor Pick Up Time for IB4
[IB 4 Pick Up Time]
Parameter Number: 126,108,_,_,_.
Access rule: Get
Data Type: USINT
Objec t Mapping: 0x384-4-18
Group: Configuration
Units : mSeconds
Minimum Value: 0
Maximum Value: 255
Default Value: 0
This parameter allows the user to view the Pick Up Time for the IB4
contactor. The Pick Up Time is the interval from when a Close or
Trip command is issued to the time that the Contactor Auxiliary
contact on IB4 opens, indicating that the contactor is closed.