B-68 Parameters
1503-UM054C-EN-P June 2013
Table B.27 Drop Out Time Settings From IB5 DIP Switches
Value Enum Text Description
0
50 ms
50 ms from IB5 DIP switches
1
75 ms
75 ms from IB5 DIP switches
2
100 ms
100 ms from IB5 DIP switches
3
130 ms 130 ms from IB5 DIP switches
4
150 ms
150 ms from IB5 DIP switches
5
175 ms
175 ms from IB5 DIP switches
6
200 ms
200 ms from IB5 DIP switches
7
240 ms
240 ms from IB5 DIP switches
Contactor Pick Up Time for IB1
[IB 1 Pick Up Time]
Parameter Number: 123,105,87,69,50.
Access rule: Get
Data Type: USINT
Objec t Mapping: 0x384-1-18
Group: Configuration
Units : mSeconds
Minimum Value: 0
Maximum Value: 255
Default Value: 0
This parameter allows the user to view the Pick Up Time for the IB1
contactor. The Pick Up Time is the interval from when a Close or
Trip command is issued to the time that the Contactor Auxiliary
contact on IB1 opens, indicating that the contactor is closed.
Contactor Pick Up Time for IB2
[IB 2 Pick Up Time]
Parameter Number: 124,106,88,70,_.
Access rule: Get
Data Type: USINT
Objec t Mapping: 0x384-2-18
Group: Configuration
Units : mSeconds
Minimum Value: 0
Maximum Value: 255
Default Value: 0
This parameter allows the user to view the Pick Up Time for the IB2
contactor. The Pick-Up Time is the interval from when a Close or
Trip command is issued to the time that the Contactor Auxiliary
contact on IB2 opens, indicating that the contactor is closed.