Manual
Parameters B-59
1503-UM054C-EN-P – June 2013
Power-Up Safety Setting for IB4
[IB 4 Power-Up Safety Setting]
Parameter Number: 106,92,_,_,_.
Access rule: Get
Data Type: BOOL
Object Mapping: 0x384-4-16
Group: Configuration
Units : -
Minimum Value: 0 = Enable
Maximum Value: 1 = Disable
Default Value: 0
This parameter allows the user to view the status of the Power-Up
Safety setting for the IB4 module. If it is enabled then the IB4
c ontac tor w ill not close the contactor if the unit powers up with a
Close command present. If it is disabled then the IB4 contactor will
close the contactor if the unit powers up with a Close command
present. See Power-up Safety in Chapter 8 and Table 8.F.
Power-Up Safety Setting for IB5
[IB 5 Power-Up Safety Setting]
Parameter Number: 107,_,_,_,_.
Access rule: Get
Data Type: BOOL
Object Mapping: 0x384-5-16
Group: Configuration
Units : -
Minimum Value: 0 = Enable
Maximum Value: 1 = Disable
Default Value: 0
This parameter allows the user to view the status of the Power-Up
Safety setting for the IB5 module. If it is enabled then the IB5
c ontac tor w ill not close the contactor if the unit powers up with a
Close command present. If it is disabled then the IB5 contactor will
close the contactor if the unit powers up with a Close command
present. See Power-up Safety in Chapter 8 and Table 8.F.