Manual

B-28 Parameters
1503-UM054C-EN-P June 2013
Trip Coil Current for IntelliVAC Base Unit #5
[IB 5 Trip Current]
Parameter Number: 50,_,_,_,_.
Access rule: Get
Data Type: FLOAT
Object Mapping: 0x384-5-10
Group: Control
Units : Amperes
Minimum Value: 00.000A
Maximum Value: 99.999A
Default Value: 00.000A
This parameter allows the user to view the average value for the Trip
coil current on the IntelliVAC Basic Module #5. This coil current is
only valid for the first 200mS after the Trip coil is energized.
Input Line Voltage for IntelliVAC Base Unit #1
[IB 1 Line Voltage]
Parameter Number: 51,41,31,21,11.
Access rule: Get
Data Type: FLOAT
Object Mapping: 0x384-1-11
Group: Control
Units : Volts
Minimum Value: 00.000V
Maximum Value: 399.999V
Default Value: 00.000V
This parameter allows the user to view the RMS value for the Input
Line voltage on the IntelliVAC Basic Module #1. The input voltage
may be either AC or DC.