Parameters B-23
1503-UM054C-EN-P – June 2013
Close Coil Current for IntelliVAC Base Unit #5
[IB 5 Close Current]
Parameter Number: 40_,_,_,_.
Access rule: Get
Data Type: FLOAT
Objec t Mapping: 0x384-5-8
Group: Control
Units : Amperes
Minimum Value: 00.000A
Maximum Value: 99.999A
Default Value: 00.000A
This parameter allows the user to view the average value for the
Close coil current on the IntelliVAC Basic Module #5. This coil
current is only valid for the first 200mS after the Close coil is
energized.
Hold Coil Current for IntelliVAC Base Unit #1
[IB 1 Hold Current]
Parameter Number: 41,33,25,17,9.
Access rule: Get
Data Type: FLOAT
Object Mapping: 0x384-1-9
Group: Control
Units : Amperes
Minimum Value: 00.000A
Maximum Value: 99.999A
Default Value: 00.000A
This parameter allows the user to view the average value for the
Hold coil current on the IntelliVAC Basic Module #1. This coil
current is only valid after the first 200mS after the Close coil is
energized and the Close coil is in the Hold state.