Manual

Parameters B-5
1503-UM054C-EN-P June 2013
Auxiliary Input Status from IntelliVAC Base Unit #4
[IB 4 Module Aux. Status]
Parameter Number: 4,4,_,_,_.
Access rule: Get
Data Type: BOOL
Object Mapping: 0x384-4-1
Group: Control
Units: -
Minimum Value: 0 = Closed
Maximum Value: 1 = Open
Default Value: 0
This parameter allows the user to view the status of the contactor
Auxiliary input from the IntelliVAC Basic Module #4. A Closed
status refers to the contactor Auxiliary input having no input voltage
which indicates that the contactor is Closed. An Open status refers to
the contactor Auxiliary input having a valid input voltage which
indicates that the contactor is Open. See the Electrical Specifications
section in Table 1.A for the voltage level for a valid Closed and
Open input.
Auxiliary Input Status from IntelliVAC Base Unit #5
[IB 5 Module Aux. Status]
Parameter Number: 5,_,_,_,_.
Access rule: Get
Data Type: BOOL
Object Mapping: 0x384-5-1
Group: Control
Units : -
Minimum Value: 0 = Closed
Maximum Value: 1 = Open
Default Value: 0
This parameter allows the user to view the status of the contactor
Auxiliary input from the IntelliVAC Basic Module #5. A Closed
status refers to the contactor Auxiliary input having no input voltage
which indicates that the contactor is Closed. An Open status refers to
the contactor Auxiliary input having a valid input voltage which
indicates that the contactor is Open. See the Electrical Specifications
section in Table 1.A for the voltage level for a valid Closed and
Open input.