Manual
8-2 Configuration/Programming
1503-UM054C-EN-P – June 2013
This set of switches defines the amount of time, after an OPEN
command has been issued, when the contactor actually drops out.
This setting may be overridden by the DeviceNet parameter
associated with each IntelliVAC base. See Appendix B for a
description.
Table 8.B – Drop Out Time Settings
DROP OUT TIME
DIP SW1
4 5 6
50 mS OFF OFF OFF
75 mS
OFF
OFF
ON
100 mS
OFF
ON
OFF
130 mS
OFF
ON
ON
150 mS ON OFF OFF
175 mS
ON
OFF
ON
200 mS ON ON OFF
240 mS
ON
ON
ON
Note: The drop off time would be 6mS longer if the close command
is applied on IB.
Table 8.A – Altitude Settings
ALTITUDE
(m)
DIP SW1
1
2
3
-1000 to 0
OFF
OFF
OFF
0 to 1000
OFF
OFF
ON
1001 to 2000
OFF
ON
OFF
2001 to 3000
OFF
ON
ON
3001 to 4000 ON OFF OFF
4001 to 5000
ON
OFF
ON
Not defined ON ON OFF
Not defined
ON
ON
ON
Contactor Drop
Out Time